EasyManua.ls Logo

Steca coolcept - Page 22

Steca coolcept
94 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Network settings, required for network communication, e. g. with
an Internet portal:
n DHCP: Switch DHCP on/off
n IP address: IP address of the inverter
n Subnet mask: Subnet mask of the inverter
n Gateway: IP address of the network gateway
n DNS address: IP address of the DNS server
n Web portal: Settings at the web portal
Web portal setting: Disabling of data transmission
and selection of a web portal
Re-transmission: Data in the inverter is transmitted a
second time
Connection check: Checks the internet connection and
indicates the result
3.3.4 Service menu
The service menu items are described below. Some items are password protected; see Fig. 5.1
(menu structure)
You can obtain the password from technical support; see
Ä
p. 84.
NOTICE!
Risk of reduced yields. In the service menu, inverter and grid parameters can be changed. The
service menu must only be operated by a specialist, who ensures that the change does not
violate applicable regulations and standards!
Power limiting
The inverter output power can be manually limited to a minimum of
500 W. When the power is manually limited, the Derating symbol is
shown in the status display and the ‘Derating’ / ‘Cause: User
default’
measurement is displayed.
EN
747,431 | Z09 | 2015-09-30
22

Related product manuals