Notes on Safety
ID 441896.05
WE KEEP THINGS MOVING
Operation manual
8
2.5 Installation and connection
The accessory installation instructions allow the following actions during the
installation of accessories:
The housing in the upper slot can be opened.
Opening the housing in another place or for other purposes is not permitted.
Installation and connection work are only permitted after the device has been
isolated from the power!
Apply the 5 safety rules in the order stated before performing any work on the
machine:
1. Enable. Also enable the auxiliary circuits.
2. Secure against restart.
3. Check that voltage is not present.
4. Earth and short circuit.
5. Cover adjacent live parts.
Afterwards you can carry out the work.
2.6 Service
Repairs must only be performed by STÖBER ANTRIEBSTECHNIK GmbH + Co.
KG. Send faulty devices with a fault description to:
STÖBER ANTRIEBSTECHNIK GmbH + Co. KG
Abteilung VS-EL
Kieselbronner Str.12
75177 Pforzheim, Germany
GERMANY
2.7 Disposal
Please comply with the latest national and regional regulations! Dispose of the
individual parts separately depending on their nature and currently valid
regulations such as, for example:
Electronic scrap (PCBs)
Plastic
Sheet metal
Copper
•Aluminum
Information
Note that the discharge time of the DC link capacitors is 5 minutes. You
can only determine the absence of voltage after this time period.