Stratus ftServer 2900 Series - Table A-2. Ftserver 2900, 4900, 6900 System Unit Specifications

Stratus ftServer 2900 Series
148 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System Specifications
A-4 Stratus ftServer 29x0, 49x0, and 69x0 Systems: Site Planning and Installation Guide (R786)
Table A-2. ftServer 2900, 4900, 6900 System Unit Specifications
Power
Input power An AC power connector
800W for each ftServer 2900 or 4900 enclosure (1600W total)
1000W for each ftServer 6900 enclosure (2000W total)
Nominal input
voltage
100-127 or 200-240 volts; 50/60 Hz.
Each CPU-I/O enclosure has a C14 (IEC 60320) input connector.
Power Factor 0.98
VA ftServer 2900 and 4900:
960 (240V x 4)
800 (100V x 8)
ftServer 6900:
1200 (240V x 5)
1000 (100V x 10)
Protective earth
ground current
3.5 mA maximum for each AC power cord
Physical Dimensions
Height 7.0 in. (17.78 cm; 4U)
Width 17.5 in. (44.45 cm)
Depth 30.1 in. (76.5 cm), with bezel, excluding rail
Weight (fully-loaded,
with 2 processors,
20 DIMMs, and
8 disks per CPU-I/O
enclosure)
System (2 CPU-I/O enclosures, shelf unit, front panel, backplane, and bezel):
120 lb (54.4 kg)
Mounting brackets: 3 lb (1.4 kg)
Environmental
Operating
temperature
41
F to 104 F (5 C to 40 C)
For every 800 ft (243.8 m) above 2000 ft (609.6 m), lower the maximum
operating temperature by 0.56F (1C).
Storage temperature -38
F to 140F (-39 C to 60 C), vented
Operating altitude 0 ft to 10,000 ft (0m to 3,048m). In China markets, regulations may limit
installations to a maximum altitude of 6562 ft (2000m).
Maximum rate of
temperature change
during operation
6.67
F (12C) per hour