STULZ Ultra-Series Humidifier Controller
(August, 2013) 37
Customer Alarm 1
Shutdown on Alarm: Yes
Ctrl Temp High Al No
Ctrl Temp Low Al No
Lim Temp High Al No
Lim Temp Low Al No
Remote Shutdown No
High Hum Stat Al Yes
Ctrl Hum High Al No
Ctrl Hum Low Al No
Lim Hum High Al No
Lim Hum Low Al No
Air Proving Al No
Water Detect Al Yes
Smoke Alarm Yes
Cab High Temp Al No
Cab Low Temp Al No
NTC2 High Temp Al No
NTC2 Low Temp Al No
Customer Alarm 1 No
Customer Alarm 2 No
Conductivity Alarm Yes
Shutdown: No
Customer Alarm 3 No
NTC3 High Temp Al No
NTC3 Low Temp Al No
NTC4 High Temp Al No
NTC4 Low Temp Al No
Customer Alarm 3 No
NTC3 High Temp Al No
NTC3 Low Temp Al No
NTC4 High Temp Al No
NTC4 Low Temp Al No
5.5.4.3.1 Customer Alarm Input Setup
The Ultra-Series controller may monitor a customer
supplied digital alarm input device and annunciate a
Customer Alarm message. One set of Customer Alarm
input terminals is standard and up to two more may be
added as an option depending on the size of the E-Ultra
controller. Upon receiving a Customer Alarm input the
controller presents a user selectable message in the alarm
display screen. A Customer Alarm message may simply
be displayed as "CUSTOMER ALARM #" as shown below,
or press () to advance to the next character and use the
() and () arrow keys to scroll through the ASCII character
set to construct a specific alpha/numeric message in the
line stating the specific alarm condition; i.e. "
GAS
DETECTION
", "
INTRUSION ALARM
", etc. The Customer
Alarm message may be setup with up to 20 characters.
Customer Alarm3 Text
5.5.4.3.2 Custom Alarm Output Setup
In addition to the Summary Alarm output to a designated
dry contact relay, the Ultra-Series controller may also
activate Custom Alarm outputs to energize separate dry
contact relay(s). Up to four custom alarm outputs may be
configured depending on the size of the E-Ultra controller.
A custom alarm output is set up by selecting specific alarm
conditions that trigger a custom alarm output from the
menu screens in this loop.
Upon entering this loop, press Enter and select the
Custom Alarm number (1 to 4) in the uppermost field.
Then press Enter to scroll through each field to select any
mix of the alarm conditions shown in the screens with the
Up/Down arrow keys. The alarm must be enabled in order
to be sensed as a custom alarm.
NOTE
On the above screen is the option to shut down
the system when this custom alarm is active.
Customer Alarm1 Text for
Custom Alarm 1 Product
Custom Alarm 1 Product
Custom Alarm 1 Product
Custom Alarm 1 Product
Custom Alarm 1 Product
Custom Alarm 1 Product