STULZ Ultra-Series Humidifier Controller
58 (August, 2013)
8 256 Fan Configured
9 512 High Water Switch State
10 1024 Low Water Switch State
11 2048 Temperature Switch State
12 4096
13 8192
14 16384
15 32768
11.0 APPENDIX B - Inputs/Outputs
The inputs/outputs available for the various size controllers are listed in the following table:
Type
Virtual Pin number
Pco3 small
Pco3 medium
Pco3 large
Use
U = Universal
N = NTC only
Option Name
Notes on basic units
DI
1
ID1 ID1 ID1 Remote shut down Remote Shutdown std. all units
DI 2 ID2 ID2 ID2 Customer Alarm 1 Customer Alarm 1 std. all units
DI 3 ID3 ID3 ID3 Air proving switch Air Proof opt all units
DI 4 ID4 ID4 ID4 Water Alarm Water detection opt all units
DI 5 ID5 ID5 ID5 Fire/Smoke detector Fire/smoke opt all units
DI 6 ID6 ID6 ID6 High limit humidistat High limit humidistat opt all units
DI 7 ID7 ID7 ID7 Customer Alarm 2 customer alarm 2 opt all units
DI 8 ID8 ID8 ID8 Freeze Alarm Freeze Alarm opt all units
DI 9 ID9 ID9 Customer Alarm 3 Customer Alarm 3 opt med & large
DI 10 ID10 ID10 Bank Select Bank select opt med & large
DI 11 ID11 ID11 open
DI 12 ID12 ID12 open
DI 13 ID13 ID13 open
DI 14 ID14 ID14 open
DO 1 NO1 NO1 NO1 Summary alarm Summary Alarm std. all units
DO 2 NO2 NO2 NO2 Custom alarm 1 Custom Alarm 1 std. all units
DO 3 NO3 NO3 NO3 Custom alarm 2 custom alarm 2 opt all units