41
When the battery works with PCS, it automatically calibrates every half year.
Calibration is done automatically by batteries and PCS given that there is
electricity in the grid or PV modules to charge and discharge batteries.
step 1 The battery automatically issues discharge instructions to PCS, which discharge the battery
to 0% SOC at rated current.
step 2 PCS charges the battery to 100% the capacity to complete the calibration of battery capacity
and SOH.
- - End
During calibration, the discharge cut-off function and charge-discharge current
limiting function are disabled.
User Manual 6 Commissioning