Loading...
46
9
Appendix
9.1 Technical Data
table 9-1 Technical parameters of high voltage LFP battery(SBR096 / SBR128 / SBR160).
Parameters SBR096 SBR128 SBR160
System Data
Battery Type
LiFePO4 Prismatic Cell
Battery
Module
3.2 kWh, 33 kg
Energy (usa-
ble)
1
9.6 kWh 12.8 kWh 16 kWh
Nominal
voltage
192 V 256 V 320 V
Operating
voltage
150 V– 219 V 200 V– 292 V 250 V– 365 V
Rated DC
power
5.76 kW 7.68 kW 9.60 kW
Max. charge/
discharge
power
6.57 kW 8.76 kW 10.95 kW
Max. charging
/ discharging
current:
continuous
30 A
Max. charging
/ discharging
current:
42 A
Depth of
Discharge
Max. 100% DOD(settable)
Short circuit
current
3500 A
Display
SOC indicator, Status indicator
Communica-
tion interface
CAN
Protection
Over / under
voltage
protection
Yes