2 Product Introduction User Manual
14
Tab. 2-6 Disconnection related to Frequency
Grid Frequency Level Maximum Time to Disconnect
(1)
f < 59.3 Hz
0.16 s
(2)
59.3 Hz <= f <= 60.5 Hz
Normal operation
f > 60.5 Hz
0.16 s
(2)
When the frequency level is out of the operational levels shown in the table, the
inverter will disconnect from the grid.
Remarks:
(1) The maximum time to disconnect refers to the interval between the
abnormal frequency level and the action of inverter (disconnect from the
grid).
(2) After the low / high frequency, the inverter will only reconnect to the grid
again when the grid frequency returns to normal operation range,
respecting the reconnection waiting time of 300 seconds.