User Manual 7 LCD Operation
51
With the password 111, the zero-export setting can only be done at the
first time. The later modification can be performed by professionals only,
please contact SUNGROW.
7.5.4 Adding the Existing Inverter
Rated-P: rated power of the existing inverter.
This function is OFF by default. If the existing
inverter is set to ON, its rated power is the lower
limit for export power setting.
ONOFF
Rated-P:
Existing Inverter
(0W
~30000W
)
2000W
7.5.5 PF Setting
The inverter is capable of operating with fixed power factor.
The PF ranges from 0.8 leading (+) to 0.8 lagging (-).
+ (Leading): the inverter is sourcing reactive power to
the grid.
- (Lagging): the inverter is sinking reactive power
from the grid.
parameters will return to the default values once the
“Param Reset” operation is performed.
Press ENT to confirm the operation.
Press ESC to discard the operation.
7.5.7 Energy Adjustment
If the accumulative value “E-total” displayed on inverter screen is different from
the value indicated on the metering device, you should adjust the energy
deviation.
(Energy Adj. value) = (Real measured value) - (E-total reading value)