User Manual 7 LCD Operation
47
7.4 Viewing Running Info
Proceed as follows to look through the detailed running information.
Main Screen (Press ENT)→Menu→Run Info (Press ENT)
Scroll pages by touching ENT / ESC.
E-total: 1999kWh
E-today: 20.0kWh
Grid Vtg:
Grid Frq:
221.7V
60.0Hz
Meter Power:
2210W
P
max
Limit:
100%
Ipv1: 2.9A
Vpv1: 250.0V
Ipv2: 2.6A
Vpv2: 244.4V
Pac:
Iac:
1338.5W
6.0A
Meter power:
+ (omitted): The inverter is sourcing power to the grid.
-: The inverter is sinking power from the grid.
P
max
limit: only indicated for the derating in the event of over-temperature,
overvoltage or over-frequency.
7.5 Advanced Settings
7.5.1 Inputting the Password
The parameter settings are protected with a password. If you want to set the
inverter’s parameters, you have to input the correct password.
Main Screen (Press ENT)→Menu (Touch ESC)→Settings (Press ENT)
Touch ESC to add the value
and Touch ENT to move the
cursor. Input the password 111.
Press ENT to confirm the password and enter the submenu.
Touch ESC to navigate down and Press ENT to confirm.
Grid Prot. Param
Param Reset
DRM Switch
Zero-export
PF
Energy Adj.
Ethernet Config
Comm. Param GND Detect
Existing Inverter