6.4.4 Static Span Calibration with Hanging Weight
Keep the belt weigher running with loading hanging weights for correcting Span Coefficient.
Put a measured hanging weight as a steady load on the belt weigher and then start belt weigher.
05[R]
R: 1-99
P110 Cal. Revs
Main Display Interface
【MENU】+【▲】【 ▼】: F2 Calibration
【ENT】+【▲】【 ▼】:4 Span Cal.Stat2
【ENT】
M
【ENT】
0010.0[kg]
R: 0.1-1000.0
P112 HangWeight
【ENT】
01.000 [m]
R: 0.001-50.000
P113 WeighLength
【ENT】