Connection of fan motor and set-up manual for frequency converter |
12-3
0-01: Language selection:
1-06: Clockwise Direction: [1] Inverse
1-10: Motor Construction: [1] PM, non-salient SPM
1-24: Motor Current: According to motor plate / Schedule
1-25: Motor Nominal Speed: According to motor plate / Schedule
1-26: Motor Cont. Rated torque: According to motor plate / Schedule
1-30: Stator Resistance (Rs): According to motor plate / Schedule
1-37: d-axis inductance (Ld): According to motor plate / Schedule
1-39: Motor Poles: According to motor plate / Schedule
1-40: Back EMF at 1000 RPM: According to motor plate / Schedule
1-42: Motor Cable Length: 3m
1-90: Motor Thermal Protection: [2] Thermistor trip
3-15: Reference 1 Source: [2] Analog input AI54
1-93: Thermistor Source: [1] Analog input AI53
3-03: Maximum Reference: According to motor plate / Schedule
3-16 + 3-17: Reference 2- and 3 Source: [0] No function
3-41 + 3-42: Ramp 1 Up and down: 30 sec.
4-19: Max. Output Frequency: According to motor plate / Schedule
4-14: Motor Speed High Limit: According to motor plate / Schedule
4-18: Current limit: 115 %
5-12: Terminal 27 Digital input: [0] No operation
5-40.0: Function Relay: [3] Drive ready/remote
5-40.1: Function Relay: [3] Drive ready/remote
6-25: Terminal 54 High Reference: According to motor plate / Schedule
14-03: Over modulation: [1] Active
14-20: Reset Mode: [2] Automatic reset x 2
0-50: LCP Copy: [1] All to LCP (Copy of Systemair factory settings to panel)
Connections:
0-10V: terminal 54-55
Start: terminal 12-18
Thermistor: terminal 50-53
Drive ready: terminal 1-2
Schedule for PM motor parameters
output |