Taco® SKV
48 302-365, Effective: June 5, 2017
© 2017 Taco, Inc.
a.Parameter 1-00 = Configuration Mode.
27.Scroll down to parameter 20-12 Reference/
Feedback Unit and press OK.
28.Change the Reference/Feedback Unit to ft WG
(press the [Down Arrow] button to reach the setting
faster). IMPORTANT: Due to the change in param-
eters, the drive will default back to metric units. It is
important to set the units back to ft WG for proper
function. Then press OK.
a.Parameter 20-12 = Reference/Feedback Unit to
ft Wg.
29.Scroll down to parameter 20-60 Sensor-
less Unit and press OK.
30.Change Sensorless Unit to GPM (press the [Up
Arrow] button to reach the setting faster). IMPOR-
TANT: Due to the change in parameters, the drive
will default back to metric units. It is important to
set the units back to GPM for proper function. Then
press OK.
a.Parameter 20-60 = Sensorless Unit to GPM.
31.Press the [Auto on] button to start the pump.
32.Press the [Status] button to get back to the main
screen.
33.The programming process is now complete and
you can run the drive.
Before