Table 14: Line Power Supply 3 x 380-480 V AC
Table 15: Line Power Supply 3 x 380-480 V AC
Table 16: With brake and load sharing 95 / 4/0
Table 17: With brake and load sharing 95 / 4/0
Line Power Supply 3 x 380-480 V AC - Normal overload 110% for 1 minute
Adjustable frequency drive
Typical Shaft Output [kW]
P11K
11
P15K
15
P18K
18.5
P22K
22
P30K
30
Typical Shaft Output [HP] at 460 V 15 20 25 30 40 15 20 25 30 40
IP20 max. cable cross-section (line power, brake, motor
and load sharing)
16, 10, - (8, 8, -) 35,-,- (2,-,-) 35 (2)
IP21, IP55, IP66 max. cable cross-section (line power,
motor) [mm
2
(AWG)]
10, 10, 16 (6, 8, 6) 35, 25, 25 (2, 4, 4) 50 (1)
IP21, IP55, IP66 max. cable cross-section (brake, load
sharing) [mm
2
(AWG)]
10, 10, - (8, 8, -) 35, -, - (2, -, -) 50 (1)
Line Power Supply 3 x 380-480 V AC - Normal overload 110% for 1 minute
Adjustable frequency drive
Typical Shaft Output [kW]
P37K
37
P45K
45
P55K
55
P75K
75
P90K
90
Typical Shaft Output [HP] at 460 V 15 20 25 30 40 50 60 75 100 125
IP20 max. cable cross-section (line power, brake, motor
and load sharing)
50 (1) 150 (300 MCM)
IP21, IP55, IP66 max. cable cross-section (line power,
motor) [mm2 (AWG)]
150 (300 MCM)
IP21, IP55, IP66 max. cable cross-section (brake, load
sharing) [mm2 (AWG)]
95 (3/0)
Line Power Supply 3 x 525-600 V AC - Normal overload 110% for 1 minute
Size: P1K1 P1K5 P2K2 P3K0 P3K7 PK40 P5K5 P7K5 P11K
Typical Shaft Output [kW] 1.1 1.5 2.2 3 3.7 4 5.5 7.5 11
IP20 max. cable cross-section (line power, motor,
brake and load sharing) [mm
2
]/[AWG]
4, 4, 4 (12, 12, 12)
(min. 0.2 (24))
IP55, IP66 max. cable cross-section (line power,
motor, brake and load sharing) [mm2]/[AWG]
4, 4, 4 (12, 12, 12)
(min. 0.2 (24))
Max. cable cross-section with disconnect 6, 4, 4 (12, 12, 12)
Line Power Supply 3 x 525-600 V AC - Normal overload 110% for 1 minute
Size: P15K P18K P22K P30K P37K P45K P55K P75K P90K
Typical Shaft Output [kW] 15 18.5 22 30 37 45 55 75 90
IP20 max. cable cross-section (line power, motor,
brake and load sharing) [mm
2
]/[AWG]
IP55, IP66 max. cable cross-section (line power,
motor, brake and load sharing) [mm2]/[AWG]
Max. cable cross-section with disconnect