12.1 Alarm Mode
SV
Alarm set value X1 / 2 / 3 (There are up to 3 sets of alarms)
ALDX
Alarm mode
Descriptio
n
Boot completed, the alarm is ON, when PVSV start the timer,
alarm and control function are turned OFF in timed out.
If the RAMP function is used, even if the RAMP SV has not
10
SOAK_A
reached the target SV, the timer will start counting as long as the
condition PVtarget SV is met.
*Please refer to Chapter 11.7
*This mode only available in ALD1 or ALD2
*In this mode, the time format is fixed to “hour.minute”
HYSX ON
11
Deviation high
OFF
SV
ALX
Formula
PV (SV+ALX) Alarm ON
PV (SV+ALX-HYSA) Alarm OFF
ON
HYSX
OFF
12
Deviation low
A
LX
SV
*
ALX must to be set to a negative value
Formula
PV (SV+ALX) Alarm ON
PV (SV+ALX+HYSA ) Alarm OFF
OFF
ON HYSX
HYSX
ON
13
Deviation high/low
ALX
SV
ALX
PV (SV+ALX) Alarm ON
Formula
PV (SV-ALX) Alarm ON
PV (SV-ALX+HYSA) Alarm OFF
PV (SV+ALX-HYSA) Alarm OFF
ON
OFF
OFF
ALX
SV
ALX
14
Band
PV (SV+ALX) Alarm ON
Formula
PV > (SV-ALX) Alarm ON
PV (SV+ALX) Alarm OFF
PV < (SV-ALX) Alarm OFF
HYSX
ON
15
Process high
OFF
ALX
Formula
PV ALX Alarm ON
PV (ALXH-HYSA) Alarm OFF
ON HYSX
16
Process low
OFF
ALX
Formula
PV ALX Alarm ON
PV (ALX+HYSA) Alarm OFF
SETA.4=0
When program execution, alarm action
17
Program run
SETA.4=1
When program end, alarm action
*This mode only available in program type controller
18
System normal
The Alert action, when system in normal condition
(no-error message)
45 FY/FU operation manual