Drainage Experiment
◆Before the test, it is necessary to ensure the unblocking state of drain pipes, and check the sealing
performance of various joints;
◆ The new room shall be subject to a drainage test before laying the ceiling;
◆ Inject a certain amount of water from the air outlet to check the drainage condition.
Precautions: the insulated cotton is used for the heat preservation of drain pipe after making sure the
unblocked drainage and no water leakage; otherwise, it may result in the generation of condensed water.
36/ 113