5.3. LAN Reset
If it is necessary to reset the supply to the factory default LAN settings, use the front panel to:
1. Press and hold the OVP/UVL button for 2 seconds
2. The 7-segment displays will show:
Lan rES
3. Release the OVP/UVL button
4. Briefly pressed and release the OVP/UVL button again.
5. The displays will briefly show:
rES 0000
and the LAN will be reset to the default settings (listed below).
If the OVP/UVL button is not pressed again, the LAN settings will not be reset
6. It may be required to AC cycle the power supply off and on. This ensures a new network
connection is established with the reset values
The default LAN settings are:
• DHCP is enabled
• If DHCP fails to get a lease, the auto-IP settings will be obtained:
IP address: 169.254.xxx.xxx (see section 4.4)
Subnet mask: 255.255.0.0
Default gateway 0.0.0.0
DNS Server 0.0.0.0
• Hostname: GENvvv-aaa-sn (see hostname in section 4.5)
• Description: “Genesys Power Supply”
• Controller Access One Client Only
• Ping Server: Enabled
• Keep-Alive 1800 Seconds (30 minutes)
• Auto-Negotiate: Automatically select network speed
• VXI-11 Discovery Enabled
• Password: None
19