TD350 Series VFD Quick start
-7-
2. Whether autotuning is needed? If possible, disconnect the motor load to carry out dynamic
parameter autotuning; if the load cannot be disconnected, perform static autotuning.
3. Adjust the acceleration and deceleration time based on actual working conditions of load.
4. Jogging to carry out device commissioning. Check whether the motor running direction is
consistent with the direction required, if no, it is recommended to change the motor running
direction by exchanging the motor wiring of any two phases.
5. Set all the control parameters, and carry out actual operation.