TD350 Series VFD Function parameter list
-194-
Function
code
Name
Detailed parameter description
Default
value
Modify
Speed
Actual detection
value
Set detection
value
Time t
t1
t2
t2=P11.15
t1<t2, so the VFD continues running
dEu
Running Fault output
Setting range: 0.010.0s
P11.16
Automatic
frequency-reducti
on during voltage
drop
01
0: Invalid
1: Valid
0
P11.17
Proportional
coefficient of
voltage regulator
during
undervoltage stall
This parameter is used to set the proportional
coefficient of the bus voltage regulator during
undervoltage stall.
Setting range: 01000
100
P11.18
Integral
coefficient of
voltage regulator
during
undervoltage stall
This parameter is used to set the integral coefficient
of the bus voltage regulator during undervoltage
stall.
Setting range: 01000
40
P11.19
Proportional
coefficient of
current regulator
during
undervoltage stall
This parameter is used to set the proportional
coefficient of the active current regulator during
undervoltage stall.
Setting range: 01000
25
P11.20
Integral
coefficient of
current regulator
during
undervoltage stall
This parameter is used to set the integral coefficient
of the active current regulator during undervoltage
stall.
Setting range: 02000
150
P11.21
Proportional
coefficient of
voltage regulator
during
overvoltage stall
This parameter is used to set the proportional
coefficient of the bus voltage regulator during
overvoltage stall.
Setting range: 01000
60