TD350 Series VFD Function parameter list
-207-
Function
code
Name
Detailed parameter description
Default
value
Modify
current of
synchronous
motor
P17.32
Motor flux linkage
0.0%200.0%
0.0%
P17.33
Exciting current
reference
Display the exciting current reference value under
vector control mode
Range: -3000.03000.0A
0.0A
P17.34
Torque current
reference
Display torque current reference value under vector
control mode
Range: -3000.03000.0A
0.0A
P17.35
AC incoming
current
Display the valid value of incoming current on AC
side
Range: 0.05000.0A
0.0A
P17.36
Output torque
Display output torque value, during forward running,
positive value is motoring state, negative value is
generating state; during reverse running, positive
value is generating state, negative value is
motoring state.
Range: -3000.0Nm3000.0Nm
0.0Nm
P17.37
Motor overload
count value
065535
0
P17.38
Process PID
output
-100.0%100.0%
0.00%
P17.39
Parameter
download wrong
function code
0.0099.00
0.00
P17.40
Motor control
mode
Ones: Control mode
0:SVC 0 - Sensorless Vector Control mode 0
1:SVC 1 - Sensorless Vector Control mode 1
(recommended SVC mode)
2:V/F (SVPWM) - Sensorless Vector Pulse Width
Modulation
3:VC - Vector ControlTens: Control state
0: Speed control
1: Torque control
Hundreds: Motor number
0: Motor 1
1: Motor 2
2