TD350 Series VFD Basic operation instructions
-57-
Calculate i
m
ACR
exciting
current
Flux linkage
observation
Current
detection
Position
observation
Speed
identific
ation
Voltage
detection
ACR
torque current
Calculate i
T
Park
conversion
PWM
pulse
Rectifier
bridge
IGBT
bridge
Motor
Park
conversio
n
Clark
conversion
φ
+
-
+
-
+
-
U
V
U
W
Uu
i
U
i
V
i
W
U
V
U
W
Uu
i
M
i
T
1w
r
1w
r
φ
i
T
R S T
Detailed parameter description
0: SVC 0 - Sensorless Vector Control mode
0
1: SVC 1 - Sensorless Vector Control mode
1 (recommended SVC mode)
2: V/F (SVPWM) - Sensorless Vector Pulse
Width Modulation
3: VC - Vector Control
Note: If 0, 1 or 3 is selected, it is required
to carry out motor parameter autotuning
first.
Motor parameter
autotuning
0: No operation
1: Rotary autotuning; carry out
comprehensive motor parameter
autotuning; rotary autotuning is used in
cases where high control precision is
required;
2: Static autotuning 1 (comprehensive
autotuning); static autotuning 1 is used in
cases where the motor cannot be
disconnected from load;
3: Static autotuning 2 (partial autotuning) ;