TD350 Series VFD Basic operation instructions
-59-
Function
code
Name
Detailed parameter description
Default
value
communication (the same as above)
9: Ethernet communication (the same as
above)
10: HDIB (the same as above)
11: EtherCAT/PROFINET/Ethernet IP
communication
12: PLC
Note: Set mode 212, 100% corresponds
to three times of rated motor current.
P03.12
Torque set by keypad
-300.0%300.0% (rated motor current)
50.0%
P03.13
Torque reference filter time
0.00010.000s
0.010s
P03.14
Source of upper limit
frequency setting of
forward rotation in torque
control
0: Keypad (P03.16)
1: AI1 (100% corresponds to max.
frequency)
2: AI2 (the same as above)
3: AI3 (the same as above)
4: Pulse frequency HDIA (the same as
above)
5: Multi-step (the same as above)
6: Modbus/Modbus TCP communication
(the same as above)
7: PROFIBUS /CANopen/ DeviceNet
communication (the same as above)
8: Ethernet communication (the same as
above)
9: Pulse frequency HDIB (the same as
above)
10: EtherCAT/PROFINET/Ethernet IP
communication
11: PLC
12: Reserved
Note: Source 1-11, 100% relative to the
max. frequency
0
P03.15
Source of upper limit
frequency setting of
reverse rotation in torque
control
0: Keypad (P03.17)
111: the same as P03.14
0