EasyManua.ls Logo

TECHTOP TD350 - V;F (SVPWM) Control Mode

TECHTOP TD350
371 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TD350 Series VFD Basic operation instructions
-61-
Function
code
Name
Detailed parameter description
Default
value
P03.32
Torque control enable
0:Disable
1:Enable
0
P03.35
Control optimization setting
Ones place: Reserved
0: Reserved
1: Reserved
Tens place: Reserved
0: Reserved
1: Reserved
Hundreds place: ASR integral separation
enabling
0: Disabled
1: Enabled
Thousands place: Reserved
0: Reserved
1: Reserved
Range: 0x00000x1111
0x0000
P03.36
ASR differential gain
0.0010.00s
0.00s
P03.37
High-frequency ACR
proportional coefficient
In the closed-loop vector control mode
(P00.00=3), when the frequency is lower
than the ACR high-frequency switching
threshold (P03.39), the ACR PI parameters
are P03.09 and P03.10; and when the
frequency is higher than the ACR
high-frequency switching threshold
(P03.39), the ACR PI parameters are
P03.37 and P03.38.
Setting range of P03.37: 020000
Setting range of P03.38: 020000
Setting range of P03.39: 0.0100.0% (in
relative to the maximum frequency)
1000
P03.38
High-frequency ACR
integral coefficient
1000
P03.39
ACR high-frequency
switching threshold
100.0%
P17.32
Flux linkage
0.0200.0%
0.0%
5.5.4 V/F (SVPWM) control mode
TD350 VFD also carries built-in V/F (SVPWM) control function. V/F (SVPWM) mode can be used in
cases where mediocre control precision is enough. In cases where a VFD needs to drive multiple
motors, it is also recommended to adopt V/F (SVPWM) control mode.
TD350 VFD provides multiple kinds of V/F curve modes to meet different field needs. Users can
select corresponding V/F curve or set the V/F curve as needed.

Table of Contents

Other manuals for TECHTOP TD350

Related product manuals