4-51
Group 22 IPM Motor Parameter Group
Control mode
Code Parameter Name Range Default Unit
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
Attrib
ute
22-00 PM motor rated power 0.00~600.00 - kW X X X X O O
200V: 50~240 220
22-01
PM motor rated
voltage
400V: 100~480 440
V X X X X O O
22-02 PM motor rated current 0.1~999.9 - A X X X X O O
22-03
PM motor ‘s pole
number
2~96 6 poles X X X X O O
22-04
PM motor’s rotation
speed
0~60000
(22-04, 22-06, only need to set
one of them, the program will
calutate the other.)
1500 rpm X X X X O O
22-05
PM motor’s maximum
rotation speed
0~60000 2000 rpm X X X X O O
22-06 PM motor frequency 0.0~400.0 75.0 Hz X X X X O O
22-07 Retain
22-08 Retain
22-09 Retain
22-10 Retain
22-11 Retain
22-12 Retain
22-13 Retain
22-14 Retain
22-15 Retain
22-16
Offset angle of the
magnetic pole and PG
origin
0~360 0 deg X X X X O X *4
0: None
1: Magnetic pole alignment and
loop adjustment
22-17 PM motor tuning
2:
Magnetic pole alignment
0 - X X X X O O
0. No Error
1. static magnetic alignment
fault
2. without PG option card
3. Rotation pole alignment is
forced to stop
4. Rotation pole alignment is
time-out.
5. Loop adjustment is time out
6. Encoder error
7. other errors of motor tuning
8. Current abnormity occurs
when aligning rotation
magnetic pole.
9. Current abnormity occurs
while loop adjustment.
22-18
Fault history of PM
motor tuning
10.Restart magnetic pole
alignment and loop
adjustment
0 -- X X X X O O *4

Table of Contents