B. Automatically switch the acceleration / deceleration time
. When the output frequency reaches set value of 00-25, it will follow the set
frequency of 00-25 to automatically switch the first and the fourth acceleration /
deceleration time. Refer to the Figure 4.3.8.
Figure 4.3.8 Automatically switch acceleration / deceleration
. When the output frequency is Fout <00-25: acceleration / deceleration time = the
first acceleration time / the first deceleration time (00-14 and 00-15).
. When the output frequency is Fout ≧00-25: acceleration / deceleration time = the
fourth acceleration time / the fourth deceleration time (00-23 and 00-24).
. The choice of multi-function digital input acceleration / deceleration time 1 (03-00 ~
03-07 are set to 10) and acceleration / deceleration time 2 (set to 30) is prior to
00-25.
00-18 Jog frequency
Range
【0.00~400.00】Hz
【0.0~1200.0】Hz
(when 00-31 = 1)
00-19
Jog acceleration time
Range
【0.1~0600.0】Sec
00-20
Jog deceleration time
Range
【0.1~0600.0】Sec
00-19 (jog acceleration time) is set to acceleration time from zero to maximum output
frequency (01-02) or (01-16), and 00-20 (jog deceleration time) is set to acceleration
time from the maximum output frequency (01 -02) or (01-16) to zero. When jog
command is effective, 00-18 is set to the jog frequency reference (factory default is set to
6.0Hz).
00- 26 Emergency stop time
Range
【0.0~6000.0】 Sec
Use multi-function digital input terminals (S1 ~ S8) to achieve deceleration stop within
the set time of 00-26.
. Multi-function digital input terminals (03-00 ~ 03-07) are set to 14: When the emergency
stop contact is ON (normally open), it achieves deceleration stop within the set time of
00-26.