4-58
A. Acceleration / deceleration time switching through the multi-function digital input terminals
. Use the multi-function digital input terminals (S1 ~ S8), based on the ON / OFF status of
terminals, select acceleration / deceleration time of operation period. The following table
shows the switching combination of acceleration / deceleration time (binary).
Table 4.3.1
Switching combination of acceleration / deceleration time
Choice of acceleration /
deceleration time 2
(Set 03-00 to 03-07 = 30)
Choice of acceleration /
deceleration time 1
(Set 03-00 to 03-07 = 10)
Acceleration time Deceleration time
0 0 Taccc1(00-14) Tdec1(00-15)
0 1 Taccc2(00-16) Tdec2(00-17)
1 0 Taccc3(00-21) Tdec3(00-22)
1 1 Taccc4(00-23) Tdec4(00-24)
0 : OFF 1 : ON
Figure 4.3.7
Acceleration / deceleration time switching through the multi-function digital input
terminals
(Example)