00- 31 Maximum frequency
Range
【0】:
400.00Hz
【1】: 1200.0Hz
The maximum output frequency Range of the inverter can be set by selecting 400Hz or
1200Hz for parameter 00-31. When setting actual panel frequency, it requires adjusting
the maximum output frequency of motor 1 of parameter 01-02 or the maximum output
frequency of motor 2 of parameter 01-16.
00- 32 Application adjustment
Range
【0】:
Disable
【1】: Water supply pump
【2】: Conveyor
【3】:
Exhaust fan
【4】:
HVAC
【5】:
Compressor
【6】:
Hoist
【7】:
Crane
(1). Water supply pump
Parameter Name Optimal value
00-00 Control mode selection 0 : V/F
11-00
Direction Lock Selection
1 : Only allow forward rotation
00-14 Acceleration time 1 1.0 sec
00-15 Deceleration time 1 1.0 sec
00-27 HD/ND selection 1 : ND
01-00 V/F curve selection F
01-04 Middle output frequency 2 of motor 1 30.0 Hz
01-05 Middle output voltage 2 of motor 1 60.0 V
07-00 Momentary stop and restart selection 1 : valid
08-00 Stall prevention function
xx0xb :
Stall prevention is valid
in deceleration
(2).
Conveyor
Parameter Name Optimal value
00-00 Control mode selection 0 : V/F
00-14 Acceleration time 1 3.0 sec
00-15 Deceleration time 1 3.0 sec
00-27 HD/ND selection 0 : HD
08-00 Stall prevention function
xx0xb :
Stall prevention is valid
in deceleration
(3).
Exhaust fan
Parameter Name Optimal value
00-00 Control mode selection 0 : V/F
11-00 Direction Lock Selection 1 : Only allow forward rotation
00-27 HD/ND selection 1 : ND
01-00 V/F curve selection F
01-04 Middle output frequency 2 of motor 1 30.0 Hz
01-05 Middle output voltage 2 of motor 1 50.0 V