07-00  Momentary stop and restart selection  1 : valid 
08-00  Stall prevention function 
xx0xb : 
Stall prevention is valid 
in deceleration
 
 
(4). 
HVAC 
Parameter Name  Optimal 
00-00  Control mode selection  0 : V/F 
11-00  Direction Lock Selection  1 : Only allow forward rotation 
00-27 HD/ND selection  1 : ND 
11-01 Carrier frequency  8.0kHz 
07-00  Momentary stop and restart selection  1 : Valid 
11-03  Selection of reducing carrier automatically  1 : Valid 
 
 
(5). 
Compressor 
Parameter Name  Optimal 
00-00  Control mode selection  0 : V/F 
11-00  Direction Lock Selection  1 : Only allow forward rotation 
00-14  Acceleration time 1  5.0 sec 
00-15  Deceleration time 1  5.0 sec 
00-27 HD/ND selection  0 : HD 
01-00 V/F curve selection F 
07-00  Momentary stop and restart selection  1 : Valid 
08-00  Stall prevention function 
xx0xb : 
Stall prevention is valid 
in deceleration
 
 
(6). 
Hoist 
Parameter Name  Optimal 
00-00  Control mode selection  2 : SLV 
00-05  Main Frequency Command Source Selection  0 : keypad 
11-43  Hold Frequency at start    3.0 Hz 
11-44  Frequency hold Time at start  0.3 sec 
00-14  Acceleration time 1  3.0 sec 
00-15  Deceleration time 1  3.0 sec 
00-27 HD/ND selection  0 : HD 
11-01 Carrier frequency  5.0kHz 
05-01  Frequency setting of speed-stage 0  6.0 Hz 
06-01  Frequency setting of speed-stage 1  30.0 Hz 
06-02  Frequency setting of speed-stage 2  60.0 Hz 
01-00 V/F curve selection  F 
03-28 Optocoupler output  5 : freuquency detection 2 
07-18  Minimum Baseblock Time  0.3 sec 
08-00  Stall prevention function 
xx1x : 
Stall prevention ineffective 
in deceleration
 
03-13  Frequency detection level 2.0 Hz 
03-14  Frequency detection width 0.0 Hz 
08-18  Selection of low-torque operation 
0: Decceleration to stop when 
low torque is detected. 
08-19  Level of low-torque detection 2 % 
08-20  Time of low-torque detection  0.5 sec