01-V/F Control Function Group
01- 00 V/F curve selection
Range
【0~FF】
When V / F mode without PG or V / F mode with PG is applied, V / F characteristic of
inverter output can be set at 01-00.
. When using V / f curve, the inverter input voltage must be set by 01-14.
. There are three ways to set V / f curve:
(1) 01-00 = 0 to E: choose the 15 default types (0 to E).
(2) 01-00 =0F, use 01-02~01-09 and 01-12~01-13, for users to define V/f curve with
voltage limitation.
(3) 01-00 = FF: use 01-02~01-09 and 01-12~01-13, for users to define V/f curve
without voltage limitation.
. The default setting of 01-00 is F, and when 01-00 is set to 1,01-02~01-09 and
01-12~01-13 have the same contents.
. When you select one of the 15 default types, the set values from 01-02 to 01-13 will
be automatically changed. There are three types of set values for 01-12 ~ 01~ 01-09
and 01-02 ~01-13. Their values are determined by the inverter capacity.
. Refer to the V / F characteristics in ~ 4.3.5.
This parameter is not affected by the initialization parameter (13-08).
Table 4.3.3 1 - 2HP V/f curve
Type Specification
01-00
setting
V/F curve
*1
Type Specification
01-00
setting
V/F curve
*1
Small start
torque
8
50Hz 0
(Hz)
22
0
50
0
1.