Table 4.3.6 Multi-function digital input setting ( 03-00 to 03-07 ) (“O”: Valid, “X”: invalid)
Function Control mode
Ref.p
age
Setti
ng
Name LCD Display
Description
V/F
V/F
+
PG
SLV SV
PM
SV
0
2-wire type (Forward
operation)
2-Wire (FWD-RUN) 2- wire (ON : Forward operation command). O O O O O
1
2-wire type (Reverse
operation)
2-Wire (REV-RUN) 2- wire (ON : Reverse operation command). O O O O O
2
Multi-speed/position
setting command 1
Muti-Spd/Pos Ref 1
Muti-Speed Reference /Position Reference 1。
O O O O O
3
Multi-speed/position
setting command 2
Muti-Spd/Pos Ref 2
Muti-Speed Reference /Position Reference 2
O O O O O
4
Multi-speed/position
setting command 3
Muti-Spd/Pos Ref 3
Multi-speed Reference /Position Reference 3
O O O O O
5
Multi-speed/position
setting command 4
Muti-Spd/Pos Ref 4
Multi-speed Reference /Position Reference 4
O O O O O
6 Forward jog run command FJOG
ON: Forward operation in jog mode (00-18).
O O O O O
7
Reverse jog run
command
RJOG
ON: Reverse operation in jog mode (00-18).
O O O O O
8
UP frequency
increasing command
UP command
ON: Command of output frequency
increasing (only used by support of
DOWN command).
O O O O O
9
DOWN frequency
decreasing command
DOWN command
ON: Command of output frequency
decreasing (only used by support of
UP command).
O O O O O
10
Acceleration/decelera
tion time selection 1
Acc/Decel Time
Selection 1
Acceleration/deceleration time selection
command1
O O O O O
11
Inhibit
Acceleration/decelera
tion Command
ACC/DEC Inhibit
ON: Acceleration/deceleration prohibition
O O O O O
12 Retain Reserved
Retain
- - - - -
13 Retain Reserved
Retain
- - - - -
14
Emergency stop
(decelerate to zero
and stop)
E-Stop
ON: Emergency stop input
O O O O O
15
External baseblock
command (rotation
freely to stop
Ext. BB
ON: Inverter base interdiction
O O O O O
16 PID control disabled PID Disable
ON: PID control disabled
O O O O O
17 Fault reset Fault Reset Fault reset O O O O O
18 Retain Reserved
Retain
- - - - -
19
Speed Search 1 (from
the maximum
frequency)
Speed Search 1
ON: Search the speed from the maximum
output frequency
OX O X O
20
Manual energy saving
function
Energy saving
ON: Manual energy saving control is
basedon the settings of 11-12 and
11-18.
O O X X O
21 PID integral reset PID I-Reset
ON: PIDintegral value reset
O O O O O
22 Retain Reserved
Retain
- - - - -
23 Retain Reserved
Retain
- - - - -
24 PLC input PLC Input
ON: Digital PLC input
O O O O O
25 External fault Ext. Fault ON: External fault alarm O O O O O
26
3-Wire sequence
(Forward/Reverse
command)
3-Wire (FWD/REV)
3-wire control (forward/reverse command)。
When the parameter is set to 26,terminal
S1 and terminal will become operation
command and stop command respectively,
and their original functions will be closed.
O O O O O