4-80
Function Control mode
Ref.p
age
Setti
ng
Name LCD Display
Description
V/F
V/F
+
PG
SLV SV
PM
SV
27
Local/Remote
selection
Local/Remote
ON: Local mode (via the digital operator)
OFF: Frequency command and operation
command will be determined according to
the setting of parameter (00-02 and
00-05).
O O O O O
28
Remote mode
selection
Remote Mode Sel
ON: RS-485 communication
OFF: Control circuit terminal
O O O O O
29
Jog frequency
command
JOG Freq Ref
ON: selection jog frequency command
O O O O O
30
Acceleration/decelerati
on setting command 2
Acc/Decel Time
Selection 2
Acceleration/deceleration time selection
command2
O O O O O
31
Inverter overheating
warning
Overheat Alarm
ON: Inverter overheat alarm (OH2)
input( will display OH2)
O O O O O
32 Sync command Sync Command
ON: Synchronous speed start
OFF: Synchronous speed close (Start other
frequency command).
O O O O O
33 DC braking
DC Brake
Command
ON: Perform DC braking
O O O O O
34
Speed Search 2 (from
the frequency
command)
Speed Search 2
ON: Search speed from set frequency
OX O X O
35 Time function input Time Input
.Set the time function at 03-33, 03-34
.Set the time function output at 03-11, 03-12
O O O O O
36
PID Soft start
ineffective
PID SFS Disable
ON: PID slow-start off
O O O O O
37 Traversing operation Wobble Run
ON: Frequency wobbling operation
O O X X O
38
Upper Deviation of
traverse operation
Upper Dev Run
ON: Upper offset of f requency wobbling
O O X X O
39
Lower Deviation of
traverse operation
Lower Dev Run
ON: Lower offset of f requency wobbling
O O X X O
40
Switching between
motor 1/motor 2
Motor 2 Switch
ON: Start motor 2
O O O O O
41 Retain Reserved
Retain
- - - - -
42 PG invalid PG Invaid
ON: Speed control without PG
X O X X O
43 PG integral reset I-Time Reset
ON: Integral value reset of speed control
with PG
XO X O O
44
Mode switching
between speed and
torque
Speed/Torque
change
ON: Torque control mode
XX X O O
45
Negative torque
command
Reverse Tref
ON: Reverse external torque
command
XX X O O
46
Zero-servo
command
Zero-Servo
ON: Zero-servo operation
XX X O O
47 Fire Mode Fire Mode
ON: Turn off hardware and software fault or
alarm protection (a special application of
HVAC)
O O O O O
48
KEB acceleration KEB Accel. ON: KEB acceleration start
O O O O O
49
Parameters writing
allowable
Write Enabled
ON: all parameters are writable
OFF: Except reference frequency (00-05)
all parameters are write-protected.
O O O O O