4-81
Function Control mode
Ref.p
age
Setti
ng
Name LCD Display
Description
V/F
V/F
+
PG
SLV SV
PM
SV
50
Unattended Start
Protection (USP)
USP
ON: After power is inputthe inverter
ignores the operation command
OFF: After power is inputthe inverter will
return the operation status before
power is cut off.
O O O O O
51
Mode switching between
speed and position
Multi Pos. Switch
ON: Switch to position mode
OFF: Switch to speed mode
X X X O O
(1). 2-wire type forward operation (setting =00).
(2). 2-wire type reverse operation (setting=01).
. Refer to the 2-wire operation mode in Figure 4.3.1.
(3). Multi-speed/position setting command 1 ( setting =02).
(4). Multi-speed/position setting command 2 ( setting =03).
(5). Multi-speed/position setting command 3 ( setting =04).
(6). Multi-speed/position setting command 4 ( setting =05).
Switch the frequency reference by multi-function digital input.
If it is SV or PMSV mode (00-00=3,4), and 03-00~07is set to 51you can use
multi-speed command to set commands of multiple segment positions.
(7). Jog frequency selection (setting =29).
Switch the frequency reference by multi-function digital input.
If it is SV or PMSV mode (00-00=3,4), and 03-00~07is set to 51you can use
multi-speed command to set commands of multiple segment positions.
.The following table 4.3.7 shows the corresponding combination.
Table 4.3.7 Multi-speed operation combination
Multi-function digital input (S1 to S8)
*4
Speed
Jog
frequency
reference
Multi-speed
frequency
4
Multi-speed
frequency
3
Multi-speed
frequency
2
Multi-speed
frequency
1
Frequency selection
1 0 0 0 0 0
Frequency command 1 ( 05-01) or
main speed frequency
*2
2
0
0 0 0 1
Auxiliary speed frequency or
frequency reference 2 ( 06-01)
*3
3 0 0 0 1 0 Frequency command 3 ( 06-02)
4 0 0 0 1 1 Frequency command 4 ( 06-03)
5 0 0 1 0 0 Frequency command 5 ( 06-04)
6 0 0 1 0 1 Frequency command 6 ( 06-05)
7 0 0 1 1 0 Frequency command 7 ( 06-06)
8 0 0 1 1 1 Frequency command 8 ( 06-07)
9 0 1 0 0 0 Frequency command 9 ( 06-08)
10 0 1 0 0 1 Frequency command 10 ( 06-09)
11 0 1 0 1 0 Frequency command 11( 06-10)
12 0 1 0 1 1 Frequency command 12 ( 06-11)
13 0 1 1 0 0 Frequency command 13 ( 06-12)
14 0 1 1 0 1 Frequency command 14( 06-13)
15 0 1 1 1 0 Frequency command 15 ( 06-14)
16 0 1 1 1 1 Frequency command 16 ( 06-15)
17 1
*1
Jog frequency command(00-18)
0 : OFF, 1 : ON, : Ignore
*1. Jog frequency terminal priority is higher than that of multi-speed reference 1 to 4.
*2. When parameter00-05=0 (frequency reference input = digital operator),
multi-speed frequency 1 will