Function  Control mode 
Ref.p
age
Setti
ng 
Name  LCD Display 
Description 
V/F
V/F 
+ 
PG 
SLV  SV
PM
SV
 
50 
Unattended Start 
Protection (USP) 
USP 
ON: After power is input,the inverter 
ignores the operation command 
OFF: After power is input,the inverter will 
return the operation status before 
power is cut off.   
O O O O O  
51 
Mode switching between 
speed and position 
Multi Pos. Switch 
ON: Switch to position mode 
OFF: Switch to speed mode 
X X X O O  
 
(1). 2-wire type forward operation (setting =00). 
(2). 2-wire type reverse operation (setting=01). 
  . Refer to the 2-wire operation mode in Figure 4.3.1. 
(3). Multi-speed/position setting command 1 ( setting =02). 
(4). Multi-speed/position setting command 2 ( setting =03). 
(5). Multi-speed/position setting command 3 ( setting =04). 
(6). Multi-speed/position setting command 4 ( setting =05). 
Switch the frequency reference by multi-function digital input. 
If it is SV or PMSV mode (00-00=3,4), and 03-00~07is set to 51,you can use 
multi-speed command to set commands of multiple segment positions. 
 
(7). Jog frequency selection (setting =29). 
    Switch the frequency reference by multi-function digital input. 
    If it is SV or PMSV mode (00-00=3,4), and 03-00~07is set to 51,you can use 
multi-speed command to set commands of multiple segment positions. 
    .The following table 4.3.7 shows the corresponding combination. 
 
Table    4.3.7 Multi-speed operation combination 
Multi-function digital input (S1 to S8) 
*4
 
Speed 
Jog 
frequency 
reference 
Multi-speed 
frequency 
4 
Multi-speed 
frequency 
3 
Multi-speed 
frequency 
2 
Multi-speed 
frequency 
1 
Frequency selection 
1 0 0 0 0 0 
Frequency command 1 ( 05-01) or 
main speed frequency
*2
 
2 
0 
0 0 0 1 
Auxiliary speed frequency or 
frequency reference    2 ( 06-01) 
*3
 
3  0  0  0  1  0  Frequency command 3 ( 06-02) 
4  0  0  0  1  1  Frequency command 4 ( 06-03) 
5  0  0  1  0  0  Frequency command 5 ( 06-04) 
6  0  0  1  0  1  Frequency command 6 ( 06-05) 
7  0  0  1  1  0  Frequency command 7 ( 06-06) 
8  0  0  1  1  1  Frequency command 8 ( 06-07) 
9  0  1  0  0  0  Frequency command 9 ( 06-08) 
10  0  1  0  0  1  Frequency command 10 ( 06-09) 
11  0  1  0  1  0  Frequency command 11( 06-10) 
12  0  1  0  1  1  Frequency command 12 ( 06-11) 
13  0  1  1  0  0  Frequency command 13 ( 06-12) 
14  0  1  1  0  1  Frequency command 14( 06-13) 
15  0  1  1  1  0  Frequency command 15 ( 06-14) 
16  0  1  1  1  1  Frequency command 16 ( 06-15) 
17 1
*1
  ─  ─  ─  ─  Jog frequency command(00-18) 
0 : OFF,    1 : ON,    ─ : Ignore 
*1.  Jog frequency terminal priority is higher than that of multi-speed reference 1 to 4.   
*2.  When parameter00-05=0 (frequency reference input = digital operator),
 multi-speed frequency 1 will 
be set by 05-01 frequency reference setting1). When parameter 00-05=1 (frequency reference