Figure 4.3.25 Multi-function digital output and related parameters
Table 4.3.8 Function talbe of multi-function digital output
Function Control way
Ref.
page
Setting
Name LCD display
Contents
V/F
V/F
+
PG
SLV SV
PM
SV
0 IDuring Running Running ON: During running (Run Command is ON) O O O O O
1
Fault contact
output
Fault
ON: Fault contact output (except CF00 and
CF01 )
O O O O O
2 Frequency agree Freq. Agree
ON: frequency agree (frequency agree width
detection is set by 03-14 )
O O O O O
3
Setting frequency
agree
Setting Freq
Agree
ON: Output frequency = allowed frequency
detection level (03-13)±allowed frequency
width(03-14)
O O O O O
4
Frequency
detection 1 (>
03-13)
Freq. Detect 1
ON: In acceleration : Output frequency >= 03-13
+ 03-14
OFF: In deceleration ,Output frequency < 03-13
O O O O O
5
Frequency
detection 2 (<
03-13)
Freq. Detect 2
OFF: In acceleration : Output frequency >= 03-13
+ 03-14
ON: In deceleration ,Output frequency < 03-13
O O O O O
6
Automatic restart
Auto Restart ON: the period of automatic restart O O O O O
7 Retain Invalid Do Func. Retain - - - - -
8 Retain Invalid Do Func. Retain - - - - -
9 Baseblock Baseblock ON: During baseblock O O O O O
10 Retain Invalid Do Func. Retain - - - - -
11 Retain Invalid Do Func. Retain - - - - -
12
Over torque
detected
Over Torque ON: Over torque detection is ON O O O O O
13 Retain Invalid Do Func. Retain - - - - -
14 Retain Invalid Do Func. Retain - - - - -
15 Retain Invalid Do Func. Retain - - - - -
16 Retain Invalid Do Func. Retain - - - - -
17 Retain Invalid Do Func. Retain - - - - -
18 PLC status PLC statement
ON: when 00-02 is set to 3 (PLC operation
command source)
- - - - -
19
PLC control
contact
Control From
PLC
ON: Control from PLC - - - - -
20 Zero speed Zero Speed
ON: Output frequency < Minimum output
frequency (Fmin)
O O O O O
21 Inverter Ready Ready ON: Inverter ready (after power on, no faults) O O O O O
22
Undervoltage
Detection
Low Volt
Detected
ON: DC bus voltage = < Low-voltage warning
detection level (07-13)
O O O O O