Figure 4.3.26 Zero-speed operation
(14).Inverter Ready (setting =21).
. Inverter operation ready after power on and no faults have occurred.
(15). Undervoltage Detection (setting =22).
. ON = the DC bus voltage of the main circuit is lower than the less voltage detection
level (07-13).
(16). Source of operation command (setting =23).
OFF
Remote mode:
When 00-02 = 1 or 2, or set any one of multi-function digital output terminals (S1 to
S8) to LOCAL / REMOTE control (setting value = 5), the contact is OFF and the SEQ
indicator of the digital operator is on.
ON
Local mode:
When 00-02 = 0, or set any one of multi-function digital output terminals (S1 to S8) to
LOCAL / REMOTE control (setting value = 5), the contact is ON and the SEQ
indicator of the digital operator is off.
(17). Source of frequency command (setting =24)。
OFF
Remote mode:
When 00-05 = 1 or 2, or set any one of multi-function digital output terminals (S1 to
S8) to LOCAL / REMOTE control (setting value = 5), the contact is OFF and the REF
indicator of the digital operator is on.
ON
Local mode:
When 00-05 = 0, or set any one of multi-function digital output terminals (S1 to S8) to
LOCAL / REMOTE control (setting value = 5), the contact is ON and the REF
indicator of the digital operator is off.
(18). Frequency reference missing (setting =26).
. when the operation command is ON and the frequency reference is 0, and when
11-41 is set to 1 (operation based on 11-42 multiplies the previous frequency
reference value), the output contact is a status of ON.
(19). Time function output (setting =27).
. For the time function operation, please refer to the descriptions of
parameter03-37 and 03-38.
(20). Traverse operation UP status (setting =28).
. For frequency wobbling operation, please refer to Parameter19-Frequency function
group
(21). During Traverse operation status (setting =29).
. By setting 28 or 29, the acceleration period or frequency wobbling operation can be
output to the function digital output terminals. For frequency wobbling control, please
refer to Parameter19 -Frequency function group.
(22). motor 2 selected (setting =30).
(23). Zero Servo Completed (setting =31).
.In zero servo status, it is ON.
(24). Communication control contacts (setting =32).