(1). Set 00-05 (frequency reference selection) to 4 (serial pulse input), take the serial pulse
input terminal PI as a frequency reference. For using pulse input as reference
frequency, please refer to Figure 4.3.5.
. By setting 03-30 (pulse input) to 0 (frequency reference), select the serial pulse input
terminal PI as a function of frequency reference, and then set the number of pulse by the
parameter03-31 (pulse input scale) equaling to maximum output frequency (01-02). If
there is interference affecting performance, you can increase the value of 03-34 (filter
time of pulse input).
When setting 03-30 to 0 (PID feedback value), you need to set 10-00 = 3 or 4,
otherwise it might appear the error of SE09 "PI settingting error".
(2). PID input of pulse input (03-30 = 1 or 2)
. Use parameter10-03 (PID control mode) to perform PID control, and set the PID
feedback value and target value.
. When setting 03-30 to 1 (PID feedback value), the pulse serial input to the control
terminal PI is regarded as the PID feedback value. When setting 03-30 to 2(PID target
value), the pulse serial input to the control terminal PI is regarded as the PID target
value. Please refer to Figure 4.3.28.
When setting 03-30 to 1 (PID feedback value), you need to set 10-01 = 3, otherwise it
might appear the error of SE09 "PI settingting error".
Figure 4.3.28 PID control
03- 35 Function setting of pulse output
Range
【
1】: Frequency command
【
2】: Output frequency
【
3】: Output frequency after the soft start
【
4】: motor speed
【5】: PID feedback
【
6】: PID input
【
7】: PG output
03-36
Scale of pulse output
Range
【
1~32000】Hz
(1). Pulse output function selection (03-35)
. For the pulse output function selection, refer to Table 4.3.10.