4-97
03- 19
Relay (R1A-R2C) type
Range
xxx0b: R1 A contact xxx1b: R1 B contact
xx0xb: R2 A contact xx1xb: R2 B contact
03- 27
UP / DOWN frequency maintaining selection
Range
0: Maintain UP/DOWN frequency when stopping.
1: Clear UP/DOWN frequency when stopping.
2: Allow frequency UP/DOWN when stopping.
03-27 is set to 0, when run command is removed, the frequency command before
deceleration will be maintained and will not be removed. The next run command will output
according to the previous recorded frequency.
03-27 is set to 1, when run command is removedthe frequency command before
deceleration will be cleared.
03-27 is set to 2, without run command, its UP/DOWN command effectively writes the
frequency command.
03- 28
Optocoupler output
Range
Range and definition are the same as those of 03-11, 03-12
03-29
Optocoupler output selection
Range
xxx0b: Optocoupler A contact xxx1b: Optocoupler B contact
03- 30 Function setting of pulse input
Range
0: Frequency command
1: PID feedback
2: PID target value
3: Retain
03-31
Scale of pulse input
Range
5
0~32000Hz
03- 32 Gain of pulse input
Range
0.0~1000.0%
03-33
Bias voltage of pulse input
Range
-100.0~100.0%
03-34
Filter time of pulse input
Range
0.00~2.00Sec
* Refer to Table 2 in Chapter 3 for the pulse input specification.
.Figure 4.3.27 shows the schematic of using pulse input function for adjustment
Figure 4.3.27 Pulse input adjustment