4-105
Figure 4.3.37 Filter time constant
(3) AI2 function setting (04-05).
. AI2 is multi-function analog input terminal. For function setting, please refer to Table 4.3.11.
Table 4.3.11 Multi-function analog input list (04-05 setting )
Function Control mode
Name Screen display
V/F
V/F
+
PG
SLV SV
PM
SV
0 Auxiliary frequency AUX.Freq Ref O O O O O
1
Frequency Reference
Gain (FGAIN)
Freq Ref Gain
Aggregated gain =
AI1 = 04-02 * FGAIN
O O O O O
2
Frequency Reference
bias (FBIAS)
Freq Ref Bias
Aggregated bias =
AI1 = 04-03 * FBIAS
O O O O O
3
Output Voltage Bias
(VBIAS)
Output Volt Bias
Aggregate output voltage
=V/F curve voltage +
VBIAS
O O X X O
4
Coefficient of
acceleration and
deceleration reduction
(K)
Tacc/Tdec Scaling
Actual acceleration and
deceleration time =
acceleration and
deceleration time
O O O O O
5 DC braking current DC Inj Current
Adjust the DC braking
current (0 ~ 100%) based
on analog input. When the
inverter rated current =
100%, DC braking current
07-07 is invalid.
O O O X O
6
Over-torque detection
level
Over Tq Level
Change over-torque
detection level based on
over-torque detection level,
at this time, 08-15 is invalid.
O O O O O
7
Stall prevention Level
During Running
Run Stall Level
Adjust the action level (30
%~200%) of stall
prevention in operation
based on analog input. The
inverter rated current =100
%.
O O X X O