4-142
4RS-485 communication error detection time (09-06).
5Stop selection of RS-485 communication failure (09-07).
= 1: Deceleration to stop by deceleration time 00-15
= 2: Coast to stop
= 2: Deceleration to stop using the deceleration time of 00-26 (emergency stop
time)
= 3: Continue to operate (only shows a warning message, press the stop
button to stop operation)
6Waiting time of inverter transmission (09-09).
Set the waiting time (see Figure 8.1.134). If the sent signals can not be
received, more time is needed to change that an command is sent after entering
the receiving status, by setting time of 09-09.
09-09 setting
24 bits long
Inverter to Master
Master to Inverter
t
Command Message
Response Message
Figure 4.3.76 Message space
10-PID Function Group
10- 00
PID target value source setting
Range
1:
AI1 given
2:
AI2 given
3:
Retain
4:
10-02 given
¾ This parameter is only used when 00- 05=5
10- 01
PID feedback value source setting
Range
1:
AI1 given
2:
AI2 given
3:
Retain
Note10- 00 and 10- 01 can not be set by the same source. If the set values are the same, then the
panel will display SE05