4-152
. Use parameter 10-29 to enable / disable PID sleep function.
10-29 = 0: PID Sleep function (sleep mode ) is disabled.
= 1: PID sleep operation is based on parameters of 10-17 and 10-18, as
described above.
= 2: PID sleep mode is enabled by multi-function digital input
10-27
PID Feedback Display Bias
Range
【
-99.99~99.99】
10-28
PID Feedback Display Gain
Range
【
0.00~99.99】
. PID feedback value can be monitored by parameter. The display unit can be set by
10-27 (PID feedback display bias) and 10-28 (PID Feedback Display gain).
. For example, the feedback value of 0 - 10V or 4 - 20mA will be displayed as
pressure. Use 10-27 to set the pressure unit (PSI unit) to 0V or 4mA feedback signal
and use 10-28 to set the pressure value corresponding to 10V or 20mA.
Refer to the figure 4.3.84 for displaying the unit conversion.
Figure 4.3.84 Display the unit conversion
Example : feedback signal: 0V = 0% = 1.0 PSI
10V = 100% = 20.0 PSI
Parameter Setting : 10-27 = 1.0 (0% feedback value )
10-28 = 20.0 (100% feedback value )
Display unit
Feedback signal