TECO A510-2001-H - Group 01 V;F Control Function Group; 01-00 V;F curve selection

TECO A510-2001-H
311 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-11
Control mode
Code Parameter Name Range Default Unit
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
Attrib
ute
00-26 Emergency stop time 0.1~6000.0 5.0 s O O O O O O
0: HD (heavy load mode)
00-27 HD/ND selection
1: ND (general load mode)
0 - O O X X X X *3
0: positive characteristic
(0~10V/4~20mA is
corresponding to 0~100%)
00-28
Command
characteristic selection
of master frequency
1: negative characteristic
(0~10V/4~20mA is
corresponding to 100~0%)
0 - O O O O O O
0: Operation based on
frequency command
1: Stop
2: Operation based on the
lowest frequency
00-29
Zero-speed operation
selection
3: Zero-speed operation
0 - X X X O O X
00-30 Retain
0: 400.00Hz
00-31 Maximum frequency
1:1200.0Hz
0 - O O X X X X *3
0: Disable
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC
5: Compressor
6: Hoist
00-32
A
pplication
adjustment
7: Crane
0 - O O O O O O
Group 01 V/F Control Function Group
Control mode
Code Parameter Name Range Default Unit
V/F
V/F
+PG
SL
V
SV
PM
SV
PM
SLV
Attrib
ute
01-00 V/F curve selection 0~FF F - O O X X X X *3
01-01 Retain
01-02
Maximum output
frequency of motor 1
40.0~400.0
40.0~1200.0 (when 00-31 = 1)
60.0 Hz O O O O O O
200V: 0.1~255.0 220.0
01-03
Maximum output
voltage of motor 1
400V: 0.2~510.0 440.0
V O O X X X X
01-04
Middle Output
frequency 2 of motor 1
0.0~400.0
0.0~1200.0 (when 00-31 = 1 )
0.0 Hz O O X X X X
200V: 0.0~255.0
01-05
Middle Output voltage 2
of motor 1
400V: 0.0~510.0
0.0 V O O X X X X
01-06
Middle Output
frequency 1 of motor 1
0.0~400.0
0.0~1200.0 (when 00-31 = 1 )
3.0 Hz O O X X X X
200V: 0.0~255.0 14.0
01-07
Middle Output voltage 1
of motor 1
400V: 0.0~510.0 28.0
V O O X X X X