4-12
Control mode
Code Parameter Name Range Default Unit
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
Attrib
ute
01-08
Minimum output
frequency of motor 1
0.0~400.0
0.0~1200.0 (when 00-31 = 1 )
1.5 Hz O O O O O O
200V: 0.0~255.0 7.5
01-09
Minimum output voltage
of motor 1
400V: 0.0~510.0 15.0
V O O X X X X
01-10
Torque compensation
gain
0.0~2.0 1.0 - O O X X X X *1
01-11 Retain
01-12
Base frequency of
motor 1
10.0~400.0
10.0~1200.0 (when 00-31 = 1)
60.0 Hz O O O O O O
200V: 0.0~255.0 220.0
01-13
Base output voltage of
motor 1
400V: 0.0~510.0 440.0
V O O X X X X
200V: 155.0~255.0 220.0
01-14 Input voltage setting
400V: 310.0~510.0 440.0
V O O O O O O
01-15
Torque compensation
time
1~10000 200 ms O O X X X X
01-16
Maximum output
frequency of motor 2
40.0~400.0
40.0~1200.0 (when 00-31 = 1)
60.0 Hz O O O O O O
200V: 0.1~255.0 220.0
01-17
Maximum output
voltage of motor 2
400V: 0.2~510.0 440.0
V O O X X X X
01-18
Middle Output
frequency 2 of motor 2
0.0~400.0
0.0~1200.0 (when 00-31 = 1)
0.0 Hz O O X X X X
200V: 0.0~255.0
01-19
Middle Output voltage 2
of motor 2
400V: 0.0~510.0
0.0 V O O X X X X
01-20
Middle output
frequency 1 of motor 2
0.0~400.0
0.0~1200.0 (when 00-31 = 1)
3.0 Hz O O X X X X
200V: 0.0~255.0 14.0
01-21
Middle output voltage 1
of motor 2
400V: 0.0~510.0 28.0
V O O X X X X
01-22
Minimum output
frequency of motor 2
0.0~400.0
0.0~1200.0 (when 00-31 = 1)
1.5 Hz O O O O O O
200V: 0.0~255.0 7.5
01-23
Minimum output voltage
of motor 2
400V: 0.0~510.0 15.0
V O O X X X X
01-24
Base frequency of
motor 2
10.0~400.0
10.0~1200.0 (when 00-31 = 1)
60.0 Hz O O O O O O
200V: 0.0~255.0 220.0
01-25
Base output voltage of
motor 2
400V: 0.0~510.0 440.0
V O O X X X X