4-13 
 
Group 02    IM Motor parameter group 
Control mode 
Code Parameter Name  Range  Default Unit
V/F 
V/F 
+PG 
SLV SV 
PM
SV
PM
SLV
Attrib
ute
02-00 
No-Load Current o
 
motor1  
0.01~600.00   -  A O  X  X X X X  
02-01  Rated current of motor1 
Modes of V/F, V/F+PG are
10%~200% of inverter’s rated 
current. Modes of SLV, SV are
25%~200% of inverter’s rated 
current.   
- A O O O O X X  
02-02 Retain 
02-03 
Rated rotation speed o
motor1  
0~60000 - 
Rpm
O O O O X X  
200V: 50.0~240.0  220.0
02-04  Rated voltage of motor1
400V: 100.0~480.0  440.0
V O O O O X X  
02-05  Rated power of motor1  0.01~600.00    -  kW O  O  O  O  X X  
02-06 
Rated frequency o
motor1  
10.0~400.0 
10.0~1200.0 (when 00-31 = 1)
60.0 Hz O O O O X X  
02-07  Poles of motor 1    2,4,6,8  4  - O  O  O  O  X X  
02-08 Retain 
02-09 
Excitation current of 
motor 1   
10.0~100.0 - % X X O O X X  
02-10 
Core saturation 
coefficient 1 of motor 1 
0~100 - % X X O O X X  
02-11 
Core saturation 
coefficient 2 of motor 1 
0~100 - % X X O O X X  
02-12 
Core saturation 
coefficient 3 of motor 1 
80~300 - % X X O O X X  
02-13  Core loss of motor 1    0.0~15. 0  -  % O  O  X  X  X X  
02-14 Retain 
02-15 
Resistance between 
wires of motor 1 
0.001~60.000 - Ω O O O O X X  
02-16 
Rotor resistanceof of 
motor 1   
0.001~60.000 - Ω X X O O X X  
02-17 
Leakage inductance o
 
motor 1   
0.01~200.00   -  mH X  X  O  O  X X  
02-18 
Mutual inductance o
 
motor 1   
0.1~6553.5   -  mH X  X  O  O  X X  
200V: 50~240  - 
02-19 
No-Load Voltage o
 
motor 1 
400V: 100~480  - 
V X X O O X X  
02-20 
No-Load Current o
 
motor2 
0.01~600.00  -  A O  X  X X X X  
02-21 
Rated current of moto
2  
10%~200% of inverter’s rated 
current   
- A O O O O X X  
02-22 
Rated rotation speed o
motor 2 
0~60000 - 
Rpm
O O O O X X  
200V: 50.0~240.0  220.0
02-23 
Rated voltage of moto
2  
400V: 100.0~480.0  440.0
V O O O O X X  
02-24  Rated power of motor 2 0.01~600.00  -  kW O  O  O  O  X X