4-26 
Group 06 Automatic Programm Operation Function Group 
Control mode 
Code Parameter Name  Range  Default Unit
V/F 
V/F 
+PG 
SLV SV
PM
SV
PM
SLV
Attrib
ute
speed-stage 14   
06-47 
Operation direction 
selection of 
speed-stage 15   
0: Stop   1: Forward  
2: Reversal   
0 - O O O X X O  
 
 
Group 07 Start /Stop Function Group 
Control mode 
Code Parameter Name  Range  Default Unit
V/F 
V/F 
+PG 
SLV SV
PM
SV
PM
SLV
ttrib
ute 
0:invalid 
07-00 
Momentary stop and 
restart selection   
1:valid 
0 - O O O O O O  
07-01 
Restart time of 
automatic reset   
0~7200 0 s O O O O O O  
07-02 
Times of automatic 
reset  
0~10 0 - O O O O O O  
07-03 Retain 
07-04 Retain 
07-05 Retain 
07-06 
DC Injection Braking 
Starting Frequency 
0.0~10.0 0.5 Hz O O O O X X  
07-07 
DC Injection Braking 
Current 
0~100 50 % O O O O X X  
07-08 
DC Injection Braking 
Time at Stop 
0.00~10.00 0.50 s O O O O X X  
0: Deceleration to stop 
1: Coast to stop   
2: DC braking stop in all fields 
07-09  Stop mode selection 
3: Coast to stop with timer 
0 - O O O O O O  
07-10 Retain 
07-11 Retain 
07-12 Retain 
200V: 150~210  190 
07-13 
Low  voltage Detection 
Level 
400V: 300~420  380 
V O O O O O O  
07-14 
Maximum 
pre-excitation time 
0.00~10.00 2.00 s X X O X X X  
07-15 Pre-excitation Level  100~200  100  % X  X  O  X X X  
07-16 
DC Injection Braking 
Time at Start 
0.00~10.00 0.00 s O O O O O O  
07-17 Retain 
07-18 
Minimum Base block 
Time 
0.1~5.0 - Sec O O O X X O  
07-19 
Speed Direction Search 
Operating Current 
0~100 50 % O X O X X O  
07-20 
Speed Search 
Operating Current 
0~100 20 % O X O X X O  
07-21  Integral time of speed 0.1~10.0  2.0  Sec O  X  O  X X O