4-26
Group 06 Automatic Programm Operation Function Group
Control mode
Code Parameter Name Range Default Unit
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
Attrib
ute
speed-stage 14
06-47
Operation direction
selection of
speed-stage 15
0: Stop 1: Forward
2: Reversal
0 - O O O X X O
Group 07 Start /Stop Function Group
Control mode
Code Parameter Name Range Default Unit
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
A
ttrib
ute
0:invalid
07-00
Momentary stop and
restart selection
1:valid
0 - O O O O O O
07-01
Restart time of
automatic reset
0~7200 0 s O O O O O O
07-02
Times of automatic
reset
0~10 0 - O O O O O O
07-03 Retain
07-04 Retain
07-05 Retain
07-06
DC Injection Braking
Starting Frequency
0.0~10.0 0.5 Hz O O O O X X
07-07
DC Injection Braking
Current
0~100 50 % O O O O X X
07-08
DC Injection Braking
Time at Stop
0.00~10.00 0.50 s O O O O X X
0: Deceleration to stop
1: Coast to stop
2: DC braking stop in all fields
07-09 Stop mode selection
3: Coast to stop with timer
0 - O O O O O O
07-10 Retain
07-11 Retain
07-12 Retain
200V: 150~210 190
07-13
Low voltage Detection
Level
400V: 300~420 380
V O O O O O O
07-14
Maximum
pre-excitation time
0.00~10.00 2.00 s X X O X X X
07-15 Pre-excitation Level 100~200 100 % X X O X X X
07-16
DC Injection Braking
Time at Start
0.00~10.00 0.00 s O O O O O O
07-17 Retain
07-18
Minimum Base block
Time
0.1~5.0 - Sec O O O X X O
07-19
Speed Direction Search
Operating Current
0~100 50 % O X O X X O
07-20
Speed Search
Operating Current
0~100 20 % O X O X X O
07-21 Integral time of speed 0.1~10.0 2.0 Sec O X O X X O

Table of Contents