4-34
Control mode
Code Parameter Name Range Default Unit
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
Attrib
ute
0: When referring to frequency
disappears, the deceleration
stops
11-41
Selection of detecting
the disappearance of
reference frequency
1: When referring to frequency
disappears, operation will be
based on the proportion of
reference frequency x 11-42
0 - O O O O O O
11-42
Disappearance level of
reference frequency
0.0~100.0 80.0 % O O O O O O
11-43 Hold Frequency at Start 0.0~400.0 0.0 Hz O O O O O O
11-44
Frequency hold Time at
Start
0.0~10.0 0.0 s O O O O O O
11-45 Hold Frequency at Stop 0.0~400.0 0.0 Hz O O O O O O
11-46
Frequency hold Time at
Stop
0.0~10.0 0.0 s O O O O O O
11-47 KEB deceleration time 0.0~25.5 0.0 s O O O O O O *1
200V: 190~210 200
11-48 KEB detection Level
400V: 380~420 400
V O O O O O O
11-49 Zero-servo gain 0~50 5 - X X O O O O
11-50 Zero-servo Count 0~4096 12 - X X O O O O
0: invalid
11-51
Braking selection o
f
zero speed
1: valid
0 - O X X X X X
11-52 Droop control level 0.0~100.0% 0.0 % X X X O O X *1
11-53 Droop control delay 0.01~2.00 0.02 s X X X O O X *1
0: don’t clear output KWHr
11-54
Output KWHr
initialization
1: clear output KWHr
0 - O O O O O O *1
0: Stop key is invalid when the
operation command is not
provided by operator.
11-55 STOP key selection
1: Stop key is valid when the
operation command is not
provided by operator.
1 - O O O O O O
0: when operator’s UP/DOWN
is invalid, it will be valid if
press ENTER after
frequency modification.
11-56 UP/DOWN selection
1: when operator’s UP/DOWN
is valid, it will be valid after
frequency modification.
0 - O O O O O O
11-57 Retain
0: invalid
11-58
Record reference
frequency
1: valid
0 - O O O O O O *1