4-50
12-08 : Parameter password = 00000 ~ 65535
This function is used to prevent parameter from being modified by disrelated personnels, keep
parameter safety.
When a password has been set, parameters cannot be modified, and it is forbidden to reset to factory
set.
(1) Setting password:
open 12-08, ”00000”is shown on keypad, input password, press” enter”,
display End.
When open 12-08 again, display “00001”, input password again, press” enter”,
display “LOC” display .
If setting is different from the first time, display “Err2”, setting failed
(2) cancel password:
open 12-08, display ”00002”,input the correct password, press” enter” key
,displayEnd, Disable the password is successed.
If typing a wrong password, display “LOC”(password is still holded)
Note: set 12-08=00000, password can’t work
Group13- Auto Run (Auto Sequencer) function group
Auto Run( sequencer) mode selection:
13-00:
0 : Disabled.
1 : Single cycle. (Continues to run from the unfinished step if restarted).
2 : Periodic cycle. (Continues to run from the unfinished step if restarted).
3 : Single cycle, then holds the speed of final step to run.
(Continues to run from the unfinished step if restarted).
4 : Single cycle. (Starts a new cycle if restarted).
5 : Periodic cycle. (Starts a new cycle if restarted).
6 : Single cycle, then hold the speed of final step to run.
(Starts a new cycle if restarted).
13-01 : Auto _ Run Mode Frequency Command 1 (0.00 ~ 400.00Hz)
13-02 : Auto _ Run Mode Frequency Command 2 (0.00 ~ 400.00Hz)
13-03 : Auto _ Run Mode Frequency Command 3 (0.00 ~ 400.00Hz)
13-04 : Auto _ Run Mode Frequency Command 4 (0.00 ~ 400.00Hz)
13-05 : Auto _ Run Mode Frequency Command 5 (0.00 ~ 400.00Hz)
13-06 : Auto _ Run Mode Frequency Command 6 (0.00 ~ 400.00Hz)
13-07 : Auto _ Run Mode Frequency Command 7 (0.00 ~ 400.00Hz)
13-16 : Auto_ Run Mode Running Time Setting 0 ( 0.0 ~ 3600.0s)
13-17 : Auto_ Run Mode Running Time Setting 1 ( 0.0 ~ 3600.0s)
13-18 : Auto_ Run Mode Running Time Setting 2 ( 0.0 ~ 3600.0s)
13-19 : Auto_ Run Mode Running Time Setting 3 ( 0.0 ~ 3600.0s)
13-20 : Auto_ Run Mode Running Time Setting 4 ( 0.0 ~ 3600.0s)
13-21 : Auto_ Run Mode Running Time Setting 5 ( 0.0 ~ 3600.0s)
13-22 : Auto_ Run Mode Running Time Setting 6 ( 0.0 ~ 3600.0s)