4-4
4.3E310 Programmable Functions List
Parameter
Group No.
Description
00- The basic parameters group
01- External terminal digital signal input function group
02- External terminal analog signal input function group
03- Preset Frequency function group
04- Start/Stop command group
05- V/F command group
06- Motor parameter group
07- Protection function group
08- Communication function group
09- PID function group
10- Assistant function group
11- Keypad display group
12- User parameter group
13- Auto Run(Auto Sequencer) function group
0- The basic parameters group
Function
Code No.
Description Range/Code
Factory
Setting
Remarks
00-00 Control Mode
0Volts/Hz
1Vector
0
00-01 Volts/Hz Patterns(V/F) 0~18 0/9 *5
00-02 Motor rotation
0Forward
1Reverse
0 *1
00-03
Main Run
Command Source Selection
0Keypad
1External Run/Stop Control
2Communication
0
00-04
Subsidiary Run
Command Source Selection
0Keypad
1External Run/Stop Control
2Communication
0
00-05
Main Frequency
Command Source Selection
0Keypad
1Potentiometer on Keypad
2External AVI Analog Signal Input
3External Up/Down Frequency Control
4Communication setting Frequency
0