4-68
Range
0.00 ~ 10.00s
10-07: Differential time for D control
10-08
PID Offset
Range
0: Positive Direction
1: Negative Direction
10-09
PID Offset Adjust
Range
0 ~ 109%
10-08 /10-09: Calculated PID output is offset by 10-09 (the polarity of offset is according to 10-08)
10-10
PID Output Lag Filter Time
Range
0.0 ~ 2.5s
10-10: Update time for output frequency.
10-11
Feedback Loss Detection Mode
Range
0: Disable
1: Enabled - Drive Continues to Operate After Feedback Loss
2: Enabled - Drive “STOPS” After Feedback Loss
10-11 =1: Feedback loss detected, continue running keypad display shows ‘PDER’
10-11 =2: Feedback loss detected, inverter decelerated to a stop and keypad display shows ‘PDER’
10-12
Feedback Loss Detection Level
Range
0 ~ 100
10-12 is feedback loss detection level. Error = Setpoint Feedback value. When the error is greater than the
feedback loss level for the time set in parameter 10-13 a feedback loss condition is detected.
10-13
Feedback Loss Detection Delay Time
Range
0.0 ~25.5s
10-13: Minimum time the error (Setpoint Feedback) value has to remain above the detection level before a
feedback loss condition is detected.
10-14
Integration Limit Value
Range
0 ~ 109%
10-14: Integral limit to prevent the PID from saturating.
10-15
Integration Value Resets to Zero when Feedback Signal Equals the target Value
Range
0: Disabled
1: After 1 Sec
30: After 30 Sec ( Range:- 1 ~ 30 Sec)
10-15=0. When PID feedback value reaches the setpoint, the integral value is not reset.
10-15=1~30.When PID feedback value reaches the setpoint, reset to 0 after 1~30 seconds and after inverter
stops. The inverter will start running again when the feedback value differs from the setpoint value.