Loading...
4-19
11-02
Carrier mode Selection
0: Mode0, 3phase PWM modulation
1: Mode1, 2phase PWM modulation
2: Mode2, 2phase soft PWM
modulation
1
-
11-03
Carrier Frequency
Reduction by temperature rise
0: disabled
1: enabled
0
-
11-04
S-Curve Acc 1
0.0 ~ 4.0
0.00
s
11-05
S-Curve Acc 2
0.0 ~ 4.0
0.00
s
11-06
S-Curve Dec 3
0.0 ~ 4.0
0.00
s
11-07
S-Curve Dec 4
0.0 ~ 4.0
0.00
s
11-08
Skip Frequency 1
0.00 ~ 599.00
0.00
Hz
*1
11-09
Skip Frequency 2
0.00 ~ 599.00
0.00
Hz
*1
11-10
Skip Frequency 3
0.00 ~ 599.00
0.00
Hz
*1
11-11
Skip Frequency Bandwidth (±)
0.00 ~ 30.00
0.00
Hz
*1
11-12
Reserved
11-13
Regeneration Prevention
Function
0: Disable
1: Enable
2: Enable (during constant speed only)
0
-
11-14
Regeneration Prevention Voltage
Level
200v: 300.0~400.0
400v: 600.0~800.0
380/760
V
11-15
Regeneration Prevention
Frequency Limit
0.0015.00
3.00
Hz
11-16
Regeneration Prevention Voltage
Gain
0~200
100
%
11-17
Regeneration Prevention
Frequency Gain
0~200
100
%
11-18
Speed loop proportion gain
0~65535
10000
11-19
Speed loop integration gain
0 ~65535
800
11-20
Speed loop differential gain
0 ~65535
0
Group12: Monitoring Parameters
Code
Parameter Name
Setting Range
Default
Unit
Notes
12-00
Extended Display Mode
00000 ~77777.
Each digit can be set to 0 to 7
00000
-
*1
0: Default display (frequency&parameters)
1:Output Current
2:Output Voltage
3:DC voltage
4:Temperature
5:PID feedback
6:Analog Signal Input. (AVI)
7:Analog Signal Input. (ACI)
12-01
PID Feedback Display format
0: Integer (xxx)
0
-
*1
1:One decimal Place (xx.x)
2:Two Decimal Places (x.xx)
12-02
PID Feedback Display Unit
Setting
0:xxx--
0
-
*1
1:xxxpb (pressure)
2:xxxfl (flow)
12-03
Custom Units (Line Speed) Value
0~65535
1500/1800
RPM
*1
12-04
Custom Units (Line
Speed) Display Mode
0:Drive Output Frequency is Displayed
0
-
*1
1:Line Speed. Integer.(xxxxx)
2:Line Speed..One Decimal Place (xxxx.x)
3:Line Speed.Two Decimal Places (xxx.xx)
4:Line Speed.Three Decimal Places (xx.xxx)