4-41
6) 03-11 =【5】. RY1 output is active when the output frequency is below the frequency detection level (03-13) and
turns off when the output frequency falls below frequency detection level.
When Output Freq.< (03-13), Relay output is ON.
FWD
REV
Setting Freq.
Setting Freq.
Output Freq.
Output Freq.
RUN RUN
ON ON
Run Command
Relay Output
(03-13)
(03-13)
ON
Hz
Time
0
Output Current Detection Level
Output Current Detection Period
03-11 =【13】.RY1 output is active when the output current value is greater than the output current
detection level (03-15).
03-15: Setting range (0.1~15.0 Amps) set based on motor rated current.
03-16: Setting range (0.1~10.0) unit: seconds.
03-16
Fixed
Value
100msec
03-15
03-11
ON
I load
100%
T
If 03-11 =【14】
In accelerating mode. RY1 output is active when the output frequency reaches the external Brake release
level set in parameter 03-17.
In decelerating mode, RY1 output is turned OFF when the actual output frequency reaches the external
Brake Engage level set in parameter 03-18.
Timing diagram for 03-17 <03-18 is shown below: