EasyManua.ls Logo

TECO L510 - Page 92

TECO L510
152 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-58
07-06
DC Injection Brake Start Frequency (Hz)
Range
【0.10 ~ 10.00】Hz
07-07
DC Injection Brake Level (%)
Range
【0~ 20】 % (Frame1/2) Based on the 20% of maximum output voltage
【0~ 100】% (Frame3/4) Based on inverter rated current
07-08
DC Injection Brake Time (Sec)
Range
【0.0 ~ 25.5】Sec
07-08/07-06 set the DC injection brake duration and the brake start frequency as shown below.
Frequency
T
07-08
07-06
RUN
Command
Run Stop
07-09
Stopping Method
Range
【0】:Deceleration to stop.
【1】:Coast to stop.
07-09 = 【0】: When a stop command is issued, the motor will decelerate to a stop using deceleration time
specified in parameter 00-15.
07-09 = 【1】: When a stop command is issued, the motor will coast to a stop. Stop time depends on motor
load and friction of the system.

Table of Contents