4-58
07-06
DC Injection Brake Start Frequency (Hz)
Range
0.10 ~ 10.00Hz
07-07
DC Injection Brake Level (%)
Range
0~ 20 % (Frame1/2) Based on the 20% of maximum output voltage
0~ 100% (Frame3/4) Based on inverter rated current
07-08
DC Injection Brake Time (Sec)
Range
0.0 ~ 25.5Sec
07-08/07-06 set the DC injection brake duration and the brake start frequency as shown below.
Frequency
T
07-08
07-06
RUN
Command
Run Stop
07-09
Stopping Method
Range
0:Deceleration to stop.
1:Coast to stop.
07-09 = 0: When a stop command is issued, the motor will decelerate to a stop using deceleration time
specified in parameter 00-15.
07-09 = 1: When a stop command is issued, the motor will coast to a stop. Stop time depends on motor
load and friction of the system.