4-58
DC Injection Brake Start Frequency (Hz)
DC Injection Brake Level (%)
【0~ 20】 % (Frame1/2) Based on the 20% of maximum output voltage
【0~ 100】% (Frame3/4) Based on inverter rated current
DC Injection Brake Time (Sec)
07-08/07-06 set the DC injection brake duration and the brake start frequency as shown below.
Frequency
T
07-08
07-06
RUN
Command
Run Stop
【0】:Deceleration to stop.
【1】:Coast to stop.
07-09 = 【0】: When a stop command is issued, the motor will decelerate to a stop using deceleration time
specified in parameter 00-15.
07-09 = 【1】: When a stop command is issued, the motor will coast to a stop. Stop time depends on motor
load and friction of the system.